Error Codes for SP-2.2
All SP2.2 Error Codes that are known
These are sensor issues, typically a missing sensor or one that is not properly connected.
The Error number relates to a location on the PCB board...
Sat, Nov 26, 2016 at 12:43 PM
P11 is a protection sensor that trips if the discharge temperature exceeds 221 F. (possibly 230 F on some models).
The chief reason for this P11 error...
Mon, Jun 8, 2015 at 5:57 PM
This is generally not a SunPump issue, because it is a sensor that says it cannot detect adequate flow through the SunPump Heat Exchanger to satisfy compres...
Sat, Dec 31, 2016 at 12:48 PM
A P3 error means SunPump has detected a water flow issue OUTSIDE of SunPump. SunPump requires 30-seconds of good flow before the compressor will start, so a...
Tue, Sep 1, 2015 at 11:41 AM
E13 is not covered in the Manual because it is rare and not very serviceable. It indicates an electrical fault on the PC Board, typically a voltage overload...
Wed, Dec 16, 2015 at 12:51 PM
This is a water flow issue, the flow sensor is not satisfied there is adequate water flow. Most of the time it is an external pump flow failure, often rel...
Sun, Dec 4, 2016 at 3:05 PM
E09 is not in the Manual, and is rare, but it is an electric voltage or frequency protection for the Motherboard to wired Controller. When the power goes ...
Sat, Nov 26, 2016 at 12:40 PM